Product Model:N6442
Overview:
This product uses the mainstream ARM kernel 32 bit microprocessor, Modbus TCP and UDP supports two protocols (choose one), can realize the rapid expansion of I/O module controller.
Protocol specification:
Modbus support Modbus TCP/UDP protocol, can quickly realize the controller with the support of the implementation of the protocol of network connection, fast I/O port expansion. Please refer to the specific use of the Modbus RTU test tools.
Main Parameter:
Processor |
32 bit |
Clock Frequency |
72MHZ |
Memory |
64KB flash, 20KB random access memory |
Power |
DC 24V |
Communication |
Modbus TCP 10/100M Modbus UDP 10/100M |
Digital Input |
Support dry contact input |
Digital Output |
Support 24VDC <3A |
Analog Input |
12 bit resolution, support 0-10V, 4-20mA input and NTC10K(B=3950)input |
Analog Output |
10 bit resolution, support 0-10V, 4-20mA output |
Model specification:
Product Model |
BI/DI |
BO/DO |
AI |
AO |
N6442 |
6 |
4 |
4 |
2 |
Product display :
Register definition specification: 1.Modbus TCP/UDP corresponding register
BI/DI---Input Status(0x02)
BI/DI Register Address |
BI/DI |
Instruction |
10001 |
1 |
Digital Input Port |
10002 |
2 |
Digital Input Port |
10003 |
3 |
Digital Input Port |
10004 |
4 |
Digital Input Port |
10005 |
5 |
Digital Input Port |
10006 |
6 |
Digital Input Port |
BO/DO—Coil Status(0x01/0x05)
BO/DO Register Address |
BO/DO |
Instruction |
00001 |
1 |
Digital Output Port |
00002 |
2 |
Digital Output Port |
00003 |
3 |
Digital Output Port |
00004 |
4 |
Digital Output Port |
AI---Input Register(0x04)
AI Register Address |
AI Port |
Instruction |
30001 |
1 |
Analog Input Port |
30002 |
2 |
Analog Input Port |
30003 |
3 |
Analog Input Port |
30004 |
4 |
Analog Input Port |
AO—Holding Register(0x03/0x06)
AO Register Address |
AO |
Instruction |
40001 |
1 |
Analog Output Port |
40002 |
2 |
Analog Output Port |
Common Question:
Q① : What is the default communication parameter for the module? A ① : The default IP of ModbusTCP module is 192.168.1.88, port number 502. Q ② : How to modify the module's IP address? A② : In the browser input module IP enters the backstage web page to modify IP.
Q③: If forgot IP , how to restore IP?
A③: In the case of power supply, dial the red dial key 2 to NO and reset, then restart after power failure. IP will revert to the default factory IP. |